APC-A1000
Front End AC-DC Power Module
AC Input: 180Vac to 264Vac, DC Outputs: 48V to 57V, 1000W |
| |
|
| |
|
The APC-A1000
series of front-end power modules is designed to operate as a key
element in a complete distributed power system.
The APC-A1000 provides 1000W of precisely regulated DC bus
voltage, in a high power density, low profile (40.8mm) package to
mount in a 1U 19’’ rack (APC-R3000).
A full complement of protection, alarm and control features
has been incorporated into the module, and this flexible feature
set makes it an excellent choice for applications requiring modular
AC-to-DC power and provides an ideal source of Bulk DC Power supply
to the APC range of high power density DC-DC Converters
Features:
- High power
density: 10.3W / in³
- Net weight:
< 2.2 KG
- Low profile:
40.8mm ( fit 1U shelf)
- Efficiency:
85%~88% typical
- Power factor
correction (meet IEC1000-3-2 requirements)
- Overvoltage
and overcurrent protection
- Overtemperature
warning and protection
- Redundant
parallel operation
- Remote on/off
and remote sense
- Active load
sharing
- Hot plug
insertion & removal
- Power fail
warning and fault alarm
- I² C for
voltage, current, temperature report & power supply ID
- Front panel
LED indicators
- 400Hz input
available
|
|

 |
|
| |
Input
Specification |
| |
|
Parameter
|
Min
|
Typ
|
Max
|
Unit
|
Condition
|
| Input
Voltage |
180
|
--
|
264
|
Vac
|
--
|
| Input
Frequency |
47
|
--
|
63
|
Hz
|
400Hz
available
with safety approvals.Consult factory for details |
| Inrush
Current (peak) |
--
|
--
|
50
|
A
|
--
|
| Power
Factor |
0.95
|
0.99*
|
--
|
--
|
50% of full load |
| Input
Leakage Current |
--
|
--
|
1.7
|
mA
|
264Vac,
50Hz |
| Lighting
Surge and Transients (damage-free operation) |
--
|
--
|
--
|
--
|
1)
IEC 1000-4-5 Level 3. 2) IEC 1000-4-4 Level 3. |
| Hold
Up Time |
20
|
--
|
--
|
ms
|
Under
80% of full load |
| EMC
(conducted) |
--
|
--
|
--
|
--
|
CISPR22
Class B, EN55022 Class B, with 3 dB margin > |
|
| |
|
| |
Line
Harmonics
Active power-factor correction circuitry ensures that this power supply
meets the requirements of IEC1000-3-2 |
| |
|
| |
Efficiency
and Power Factor vs. Input Voltage at full load |
| |
|
Input
Voltage
|
Efficiency
(Typical)
|
Power
Factor (Typical)
|
|
180Vac
|
85%
|
0.98
|
|
220
Vac
|
86%
|
0.98
|
|
240Vac
|
87%
|
0.98
|
|
264Vac
|
88%
|
0.98
|
|
| |
Notes:
When using this table to calculate line cord requirements, allow at a minimum,
an extra 3% for variations between units. Actual measured results will depend
upon the harmonic content of the input voltage waveform. |
| |
|
| |
Download
Datasheet for the APC-A1000 here (pdf)
|
| |
|
| |
Click